Installation
DIP switch setting

Name
Function
SW1
Not available
SW2
Reset
SW3
Not available
(TELE)
SW4
Configuration
SW5
Configuration
SW6
Configuration
SW7
Options 2
Options 1
SW8
(Application type)
SW9
Not available
SW10
CHL-MBS-01 address
SW11
H-LINK DSW
D4, D11
H-LINK
D7
Power
D9/D10
Not used
D12
MODBUS
D13
Operation
12
Factory setting
-
-
-
PMML0301A rev.0 - 09/2013
All in off (no function)
Reset button. To be used in case of program has been locked
Factory purposes. Never change it
Setting functions
Setting functions
Setting functions
SW7-1: 0FF - Not used / ON - Always.
SW7-2: Not used
SW7-3: OFF - Parity disabled / ON - Parity enabled
SW7-4: OFF - Even parity / ON - Odd parity
SW7-5: OFF - 19200 Bps / ON - 9600 Bps
SW7-(6~8): Not used
SW8-1: 0FF Chiller AH
SW8-1: ON Chiller AG2(B)/WG2/CLG2
To be set according units application
SW8-2~8: Not used
All in off (no function)
CHL-MBS-01 address from 1 to 32 by pins 1 to 5
2-Pins DSW
SW11-1: H-LINK end resistance
SW11-2: Not used
H-LINK transmission
Power supply ON/OFF
-
Modbus communication in RS485
Normal software operation
Description