Ex-DQ 2x23.1VDC/20mA
Termi
Assig
Termi
nal
nmen
nal
t
1
DQ.0+ 2
3
4
DQ.0-
5
6
Res
7
Res
8
Equipping
• Check the I/O module for damage! You may only plug undamaged I/O
modules onto the BaseUnit.
• The coding element on the BaseUnit latches into place the first time that a
I/O module is plugged in. This prevents the insertion of a wrong module.
This mechanical coding may not be changed.
• When configuring the ET 200SP HA and the ET 200SP, you must observe
the permissible number of I/O modules (see the respective operating
instructions).
WARNING
Permissible number of I/O modules
When configuring the ET 200SP HA and the ET 200SP, you must observe the
rules specified below for the maximum configuration and load of the Ex
power modules.
Load on the Ex power modules
14
Table 1-1
Pin assignment of Ex-DQ 2x23.1VDC/20mA
Assig
Explanations
nmen
t
DQ.1+ •
Terminals 1; 2
DQ.1-
DQ.n+: Output signal, channel n (0;1)
Res
Terminals 3; 4
Res
DQ.n-: Ground, channel n (0;1)
Terminals 5; 6; 7; 8
Res: Reserve
Ensure that the current consumption of the Ex I/O
modules of an Ex module group does not exceed the
permissible output current of the Ex power module.
Ex-DQ 2x23.1VDC/20mA
A5E50377641-AB, 03/2023