Statement 7005—Intra-building Lightning Surge and AC Power
Fault
The intra-building port(s) of the equipment or subassembly must not be metallically connected to interfaces that
Warning
connect to the OSP or its wiring. These interfaces are designed for use as intra-building interfaces only (Type 2
or Type 4 ports as described in GR-1089-CORE) and require isolation from the exposed OSP cabling. The addition
of Primary Protectors is not sufficient protection in order to connect these interfaces metallically to OSP wiring.
Statement 7012—Equipment Interfacing with AC Power Ports
This equipment shall be connected to AC mains provided with a surge protective device (SPD) at the service
equipment complying with NFPA 70, the National Electrical Code (NEC).
Statement 7013—Equipment Bonding Networks CBN
This equipment is suitable for installations utilizing the insert Common Bonding Network (CBN).
Note
Statement 7016—Battery Return Conductor
The battery return conductor of this equipment shall be treated as DC Isolated (DC-I).
Statement 8015—Installation Location Network
Telecommunications Facilities
This equipment is suitable for installation in Network Telecommunications Facilities.
Regulatory Compliance and Safety Information—Cisco Firepower Management Center 1000, 2500, and 4500
10
Regulatory Compliance and Safety Information—Cisco Firepower Management Center 1000, 2500, and 4500