timer {rule_num} name set "{name}"
timer {rule_num} name show
timer {rule_num} {FROM=0|UNTIL=1} set "{yyyy-
mm-dd}"
timer {rule_num} {FROM=0|UNTIL=1} show
timer {rule_num} trigger jitter set {0..65535}
timer {rule_num} trigger jitter show
timer {rule_num} trigger random set {0..100}
timer {rule_num} trigger random show
timer {rule_num} trigger {HOUR=0|MIN=1|SEC=2|
DAY=3|MON=4|DOW=5} set "{time_date_list}"
timer {rule_num} trigger {HOUR=0|MIN=1|SEC=2|
DAY=3|MON=4|DOW=5} show
timer {rule_num} action mode set {SWITCH=1|
CLI=2}
timer {rule_num} action mode show
timer {rule_num} action {SWITCH1=0|
SWITCH2=1} {OFF=0|ON=1} set "{port_list}"
timer {rule_num} action {SWITCH1=0|
SWITCH2=1} {OFF=0|ON=1} show
timer {rule_num} action delay set {0..65535}
timer {rule_num} action delay show
timer {rule_num} action console set "{cmd}"
timer {rule_num} action console show
timer {rule_num} action hash set "{data}"
timer {rule_num} action hash show
timer {rule_num} delete
timer delete all
vt100
vt100 echo set {OFF=0|ON=1}
vt100 echo show
vt100 numeric set {OFF=0|ON=1}
vt100 numeric show
vt100 reset
Hinweise
1. Legacy - Der Befehl ist von einer neueren Version abgelöst worden
2. Befehl kann auf allen Ebenen ausgeführt werden
3. Die Ausgabe kann 2 Zeilen umfassen - die erste Zeile zeigt den aktuellen Zustand,
die zweite Zeile den Status nach einem Neustart
4. Die Ausgabe kann mehrere Zeilen umfassen
5. Bitte die Energie Sensor Tabelle konsultieren, um den richtigen Index zu finden
6. Bitte die Tabellen Externer Sensor Feld und Externer Sensor Typ konsultieren,
um den richtigen Index zu finden
Energie Sensor Tabelle "{energy_sensor}"
Index
Beschreibung
0
Absolute Active Energy
1
Power Active
2
Voltage
3
Current
4
Frequency
5
Power Factor
6
Power Angle
7
Power Apparent
8
Power Reactive
9
Absolute Active Energy Resettable
10
Absolute Reactive Energy
11
Absolute Reactive Energy Resettable
12
Reset Time - sec. since last Energy Counter Reset
13
Forward Active Energy
14
Forward Reactive Energy
Expert Power Control 8221/8226
sets name of rule
shows name of rule
sets date range of rule
shows date range of rule
sets jitter for rule
show jitter of rule
sets probability for rule
shows rule probability
sets time date list
shows time date list
sets switch or cli cmd
shows if switch or cli cmd
sets port list for switch cmd
shows port list for switch cmd
delay between cmds
shows delay between cmds
sets cmd string
shows cmd string
sets action binary form
shows action binary form
delete one timer
delete all timer
enters cmd group "vt100"
sets console echo state
shows console echo state
sets numeric mode
shows numeric mode state
resets terminal
Einheit
Wh
W
V
A
0.01 hz
0.001
0.1 degree
VA
VAR
Wh
VARh
VARh
s
Wh
VARh
84