TECHNICAL DATA
6.
Communication
Power Supply
Bus cable
Bus current consumption
Control elements
Display elements
Actuation elements
Maximum switchover
current
Maximum power
for load type
Ambit of use
Operating temperature
Storage temperature
Relative humidity
Bus connection
Electrical connections
Protection rating
Dimensions
Reference standards
Certification
KNX BUS
Via KNX BUS, 29 V dc SELV
KNX TP1
5 mA max
1 mini programming key
1 relay local command button
1 red programming LED
1 green output status signal LED
1 NO/NC relays with potential free
contact
16A (cosφ=1)
Incandescent lamps (230V AC): 1500W
Halogen lamps (230V AC): 1500W
Loads controlled by electronic
transformers: 600VA
Uncompensated fluorescent loads:
400VA
Energy efficient lamps (compact
fluorescent): 8x23W
For compensated fluorescent lamps
and all other loads not indicated here,
you are advised to use a support relay
Indoors, dry places
-5 ÷ +45 °C
-25 ÷ +70 °C
Max 93% (no condensation)
2-pin coupling terminal - Ø 1 mm
Screw terminals, Max cable section:
4 mm
2
IP20
2 Chorus modules
Low Voltage Directive 2006/95/EC
Electromagnetic Compatibility Directive
2004/108/CE
EN50428, EN50090-2-2
KNX