Troubleshooting
Fault
The control system
does not activate.
The cabin does not
heat up.
The cabin light fails to
activate when
switched on.
9.
Spare parts
Article no.
3070144
30601112
50701115
3060103
PAGE 36
All repair and servicing work must be carried out by persons or
organizations expressly authorized to do so by the manufacturer.
Cause
No mains power.
Room temperature of control
system <0 ºC or >40 ºC.
The safety temperature-limiter
(STL) has been activated.
The master switch is not
connected or the
temperature controller is
turned fully anticlockwise.
Light defective.
There is no mains power.
The fuse has blown.
Spare part
Easy Control system
Power unit 9 kW
Operating instructions for Easy Control system
Operating instructions for Easy Control system - export version
STB2
Remedy
Check FI switch and power supply fuse.
Set room temperature of control system to
>0 ºC or <40 ºC.
Do not make any further use of the control
system.
Contact customer service.
Activate the control system at the master
switch and turn the temperature controller as
far as it will go to the right.
Replace lamp.
1.
Disconnect the control system from the
mains supply.
2.
Replace with a lamp of the same
wattage.
Check the FI switch and power supply fuse.
Replace fuse.
1.
Disconnect the control system from the
mains supply.
2.
Replace fuse (1.25 AT) contact
customer service.
Easy Control
50701116/10.05