Proceed as follows:
1. Click on the "Recalibrate" button.
The first calibration arrow appears on the display.
2. Touch it briefly and within five seconds exactly on the tip of the calibration arrow ①.
Confirm the calibration with a green check mark at this location; the next calibration crosshairs will be displayed.
3. Touch all the other calibration arrows that are shown on the display.
Calibration crosshairs are displayed in the central area of the touch screen.
4. Touch exactly the center of the calibration crosshairs ② briefly and within five seconds.
Confirm the calibration with a green check mark at this position.
MP 377 15" Touch daylight readable
A5E02341631-03, 06/2009
15