Function and features
The AS-i AirBox is a slave in the AS-i system (AS-i profile S 3.F). The elec-
trical inputs are rated for the connection of binary 2-wire or pnp 3-wire
sensors to IEC 947-5-2. As an alternative, mechanical position switches
can be connected between pin 1 and pin 2/4.
• Integrated sensor supply (a total of 100mA per module)
• Plug-in sensor connection
• AS-i connection via EMS module lower part
• Connection to pneumatic system via push fit tube connector Legris
3000/8mm, outside calibration according to CETOP standards RP 54P
• Operation with compressed air of 3...8bar including any pressure
peaks (Pressure peaks >8bar can cause permanent leaks and irrepa-
rable damage of the AirBox).
sensor connection I-1
flat cable yellow
pneumatic output (2,4)
NO/NC selectable
Mounting
Address assignment by means of the addressing unit.
Fix the module onto the addressing unit. Assign a free address between
1 and 31; the factory preset is 0.
Mount the module onto the wired module lower part of the AS-i net-
work, tightening torque 0.8Nm.
6
LED I-1, I-2
2
4
LED O-3
exhaust 1 [P]
exhaust 3 [R]
sensor connection I-1
I-1
I-2
PWR
LED AS-i PWR
screw for manual override
O-3