Explosionsgeschützte druckfeste bausteine
Vorschau ausblenden Andere Handbücher für CROUSE-HINDS-Serie:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Contact arrangement
Overvoltage arrester
Contact arrangement
Multi-function relay
Contacts for functions 11, 21 and 42
Contacts for functions 12, 16 and 22
Contact arrangement
Motor starter 4 kW
22
Flameproof module series, GHG 61. .... R....
10.13 Overvoltage arrester
EC-Type Examination Certificate:
Explosion protection:
Rated operating voltage:
Rated discharge surge current I
Limiting discharge current I
Attack time t
:
A
Residual voltage at mains operation voltage:
Extinction voltage U
to earth (PE):
L
Back-up fuse:
Tripping current of cut-off device I
Short-circuit protection (with 63 A back-up fuse): 25kA
Terminal cross section:
Component size:
Weight:
Monitoring device (optional):
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
10.14
Multi-function relay
EC-Type Examination Certificate:
Explosion protection:
Rated voltage:
Control voltage:
Rated current:
Rated switch capacity:
Back up fuse:
Time ranges (optional):
Control functions:
Terminal cross section:
Component size:
Weight:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
10.15
Motor starter 4 kW
C-Type Examination Certificate:
Explosion protection:
Rated voltage:
Control voltage:
Rated current:
Rated switching capacity Main contacts AC 3: 230V/2.2kW
Rated switching capacity Aux. contacts AC 11: 230V / 4A
Terminal cross section:
Switching contacts 1, 2, 3, 4, 5, 6,
Control contacts A1, A2
Aux. contacts optionally 21,22, 23,24, 33 34
Component size:
Weight:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
PTB 98 ATEX 1087U
Ex de IIC/IIB Gb
max. 275V AC
:
max. 5kA
SN
:
max. 25kA
S
25ns
approx. 1000V
280V AC
max. 63A gL
:
5A
ÜA
eff
Switching contacts A1, A2
Control contacts 15,16,18
1
approx. 0.5 kg
Marking under the glass
PTB 98 ATEX 1087U
Ex de IIC/IIB Gb
up to 440V AC
12V - 275V* AC
(*further control voltages on request)
6A
AC 11
DC 11
24V/1A,
6A gL
0.05 - 1sec.; 0.15 - 3sec.; 0.5 - 10sec.;
3 - 60sec.;
0.15 - 3h; 0.5 - 10h;
11
12
16
21
22
42
Main contacts
Control contacts
Aux. contacts
2
ca. 0.94kg
PTB 98 ATEX 1087U
Ex de IIC/IIB Gb
up to 690V AC
12V - 275V* AC
(*further control voltages on request)
Main contacts
Aux. contacts
max. 2x 10mm²
max. 2x 2.5mm²
max. 2x 2.5mm²
3
approx. 1.72kg
max. 2x 10mm² / 3.0 Nm
max. 2x 2.5mm² / 1.5 Nm
12V - 240V DC
230V/3A
440V/3A
60V/ 0.35A,
220V/0.20A
0.5 - 10min.; 3 - 60min.;
3 - 60h
-
delayed pick-up
-
delayed reset
-
delayed pick-up and reset
-
cut-in wiping
-
cut-off wiping
-
blinking
max. 2x 10mm²/ 3.0 Nm
max. 2x 2.5mm²
/ 1.5 Nm
max. 2x 2.5mm²
/ 1.5 Nm
12V - 230V DC
up to 20A
up to 6A
400V/4kW
690V/4kW
/ 3.0 Nm
/ 1.5 Nm
/ 1.5 Nm