12.1 EtherNet/IP-Objektklassen
Instance-Attribut (Instanz 1)
Attribut
Name
1
Vendor ID
2
Device Type
3
Product Code
4
Revision
5
Status
6
Serial Number
7
Product Name
110
Zugang
Datentyp
Get
UINT
Get
UINT
Get
UINT
Get
USINT, USINT
Get
WORD
Get
UDINT
Get
STRING
12 CIP-Objektklassen
Beschreibung
Vendor Identification
Indication of general type of product
Identification of a particular product of
an individual vendor
Structure with major and minor
revision
Summary status of device:
b0: Owned
b1: Reserved ("0")
b2: Configured
b3: Reserved ("0")
b4 .. 7: Extended Device Status
0 = Self-Testing or Unknown
1 = Firmware Update in Progress
2 = At least one faulted I/O connection
3 = No I/O connections established
4 = Non-Volatile Configuration bad
5 = Major Fault
6 = At least one I/O connection in
RUN mode
7 = At least one I/O connection
established, all in IDLE mode
8 = Unused (valid only for instances
grater than "1")
9 = Reserved
10 .. 15 = Vendor specific
b8: Minor Recoverable Fault
b9: Minor Unrecoverable Fault
b10: Major Recoverable Fault
b11: Major Unrecoverable Fault
b12 .. 15: Reserved ("0")
Serial number of device
Human readable identification