Hygrostat and other control options

Hygrostat
The control is prepared for connection of a hygrostat which is placed in the room to be
dehumidified or in the supply air duct – (air inlet).
Hygrostat is available as accessory.
Connection of
Please follow this procedure to connect a hygrostat.
hygrostat
The outlet for the hygrostat is 12 V.
Room thermostat
The control is prepared for connection of a room thermostat which is placed in the
room to be dehumidified or in the supply air duct – (air inlet).
Room thermostat is available as accessory.
Connection of room
Please follow this procedure to connect a room thermostat.
thermostat
The outlet for the room thermostat is 12 V.
28
Step
1
The hygrostat is connected to the terminals 3 and 4 after having taken away
the bridge
Step
1
The thermostat is connected to the terminals 5 and 6 after having taken away
the bridge
Action
Action