Herunterladen Inhalt Inhalt Diese Seite drucken

Eaton SM87BG Technische Bedienungsanleitung Seite 7

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 22
SM87PB General arrangement
SM87PB units - operation
The unit is operated by lifting the flap on the front of the
cover, then depressing the steel actuator underneath.
Depending on the unit type ordered, the actuator will
either remain in its depressed position (latching versions)
or return to its original position (momentary versions).
SM87PB Turn and push general arrangement
105 ±1 CRS
'T'
122 ±1
'L'
TAG LABEL
(OPTIONAL)
'B'
122 ±1
SM87PB Turn & push - operation
The unit is operated by lifting the flap on the front cover,
then turning the actuator clockwise 90° and depressing
the actuator. The actuator will remain in its depressed
position.
9 1 FIXING HOLES
4 POSITIONS
DUTY LABEL
'R'
105 ±1 CRS
Call points sM87BG/pB TM146 January 2023 www.eaton.com
SM87PB units - resetting procedure
On units with a latching mechanism, once operated,
the actuator remains in its depressed position. To reset
the call point, lift the flap on the front of the cover and
insert the key (provided with the unit) into the slot in
the front face of the actuator. The key should be turned
slightly to locate it in the actuator and pulled back to the
initial position. The key can then be removed and the
flap lowered.
87.5 ±2 (A)
81 ±2 (S)
36.5 ±1 (A)
30 ±1 (S)
138.5 ±3 (A)
132 ±3 (S)
SM87PB Turn & push – resetting procedure
Once operated the actuator remains in its depressed
position. To reset the call point, lift the flap on the front
cover and pull the actuator out from its depressed
position. Turn the actuator anti-clockwise 90°. The lift flap
can then be lowered.
Call points SM87BG/PB
English
3

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Sm87pb

Inhaltsverzeichnis