Herunterladen Inhalt Inhalt Diese Seite drucken

Rectification Of Operating Faults; General - Pfannenberg DTS 6801-Serie Betriebsanleitung

Anbau- und einbau-kühlgeräte
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
ENG
7

Rectification of operating faults

7.1

General

NOTE
Flashing of the red LED light on the controller card is not a fault indication or error message.
The red LED light indicates that the cooling unit is carrying voltage.
Fault
Unit does not cool, evaporator fan
(internal) running
Unit does not cool sufficiently
Unit only cools sometimes.
Condensate formation in the switch
cabinet
Condensate does not drain
Condensate drips from the unit.
Tab. 15: General operating faults
Operating Manual | Attachment and Installation Cooling Units | Multi Controller (MC) – 400 / 460 V, 3~ | 086100126
Possible causes
Temperature setting too high.
Application limits exceeded.
Low refrigerant level.
Heat exchanger contaminated.
Evaporator fan (internal) defective.
Condenser fan (external) defective.
Air circulation in switch cabinet
disrupted.
DIP-switch set incorrectly or defective.
Blow-out temperature too low.
Switch cabinet is not sufficiently sealed.
Condensate drain is blocked.
Switch cabinet is not sufficiently sealed.
Condensate drain is blocked.
Remedial measures
Check temperature setting.
Check ambient air temperature and
internal load.
Call authorized specialist personnel,
check the unit for leaks.
Cleaning the heat exchanger.
Call authorized specialist personnel;
change fan.
Check installations and circulation
channels in the switch cabinet.
Check the air inflow and outflow from the
cooling unit into the inlet and outlet
openings of the switch cabinet.
Check DIP-switch and cable
connections.
Set higher temperature on the DIP-
switch.
Close switch cabinet door.
Rectify any leaky areas or seals on the
switch cabinet.
Check temperature setting.
Clean the condensate drain.
Check whether the condensate drain
hose is free of kinks and installed on a
gradient.
Rectify any leaky areas or seals on the
switch cabinet.
Clean the condensate drain.
Check whether the condensate drain
hose is free of kinks and installed on a
gradient.
63/74

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Dti 6801-serie

Inhaltsverzeichnis