Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - ASO Safety Solutions ELMON relay 41-312 Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

ELMON relay 41-312 / 41-812
Safety Relay

13. Technical data

Supply voltage
Mains voltage
U
Netz
Supply type
Low voltage
U
E
Power consumpti on P
Netz_max
P
E_max
P
E_max
Safety relay
Nominal current DC
Nominal current AC
Mechanical life-ti me
Switch-off delay
(reacti on ti me)
Switch-on delay
Uti lizati on category
Housing
Dimensions (HxWxD)
Housing
Housing incl . cable clamps
Protecti on type
with M16-cable clamps
with M16-blanking plug
Protecti on class
Contaminati on degree
Overvoltage category
Rated insulati on voltage
Rated impulse voltage resistance
Weight
Temperature range
Connecti on cable cross-secti on
Certi fi cati ons
ELMON relay 41-312 (41-812)
Electronics
Electromechanics
EC type-examinati on no.:
44 205 13176203
ELMON relay 41-312: 230 V AC 50/60 Hz
ELMON relay 41-812: 115 V AC 50/60 Hz
Typ X
24 V AC/DC ±10%
2,2 VA 230 V AC (oder 115 V)
1,5 W 24 V DC
1,2 VA 24 V AC
3 A (30 V DC)
1 A (230 V AC)
>10
actuati ons
6
< 12 ms
500 ms (Power on 700ms)
AC-15 (230V AC; 1A; 550000 Op.)
DC-13 (30V DC; 3A; 120000 Op.)
ABS, transparent lid
(polycarbonate)
120 x 80 x 56 mm
120 x 102 x 56 mm
IP65
IP54
II (protecti ve insulati on)
2
III
250 V
4,00 kV
350 g
-20 °C to +55 °C
single- or fi ne-stranded cable
0,75-1,5 mm
2
EN ISO 13849-1:2008 Category 3 PL e
(MTTFd 236 years, DC 99 %)
EN 62061:2013 SILCL 3
(PFHd 8,59E-09 1/h)
MTTFd 625 years, DC 99 %
MTTFd 380 years, DC 99% (Nop 52560)
Certi fi cate no.:
44 780 13 xxxxxx
Terminati ng resistor – sensor
Nominal value
Upper switching
point
Lower switching
point
Auxiliary relay
max. switching current
Mechanical life-ti me
Operati ng mode RL:
Switch-on delay
Operati ng mode RL:
Switch-on durati on
With the RLU version the signal relay switches synchronously
to the operati on of the sensor.
B10d 2000000
Test report no.:
3512 6372
R
= 8,2 kΩ
Nom
R
> 12,0 kΩ
AO
R
< 5,0 kΩ
AU
2 A (30 V DC)
1 A (230 V AC)
> 10
actuati ons
6
0,5 Sek.
3 Sek.
23

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Elmon relay 41-812

Inhaltsverzeichnis