10. Commissioning and function testing

After a corresponding connection of all electrical connections and switching on the supply voltage, the
system / machine must be checked for correct functionality.
After successful commissioning, the safety STOP1 and STOP2 outputs are driven (relay contacts "closed").
An operation of the signal transmitter causes an opening of the relay contacts.
The signaling relay (AUX connection) switches in accordance with the present DIP switch position. This is
indicated by means of the yellow AUX LED .
The safety system must be inspected by competent specialists at suitable intervals. The check must be
documented in a way that allows it to be traced at any time. The requirements of the system / machine
manufacturer are to be taken into account and observed.

11. Fault diagnosis

If the supply voltage is correctly wired and applied, only the green Power LED may be lit up. If the red LED
illuminates, there is a fault in the system which can be delimited by means of the LED.
LED
green LED
Power
does not light up
green LED
Power
flashes cyclically
(pulse output)
red LED
Fault
lights up
red LED
Fault
fast flashing
defectively connected or defective
red LED
Fault
slow flashing
* If the fault is not found in the wiring, the function of the electronic system can be checked by applying
a resistance of 8.2 kΩ to the sensor-input on the switching device. Subsequently, if the electronics work
perfectly, the sensor must be checked by means of an ohmmeter. For this purpose, the connection of
the sensor to the switching device must be separated and connected by means of an ohmmeter. In the
case of a non-operated sensor the resistance must be 8.2 kΩ ± 500 Ω. If the sensor is operated, the
resistance must not exceed 500 Ω.

12. Decommissioning and disposal

The products manufactured by ASO are exclusively intended for commercial use (B2B). At the end of use, the
products must be disposed of according to all local, regional and national regulations. ASO is also happy to
take back the products and disposes of them properly.
22
Fault
Supply voltage is missing,
too low or
incorrectly connected .
Internal fault is indicated
by the number of pulses .
The corresponding sensor
is recognized
as being operated .
Sensor circuit interrupted,
sensor not connected,
Fault self-retaining

Fault removal

Check connections and supply voltage:
- 230 V AC (or 115 V) at terminals L1 N or
- 24 V AC/DC at terminals 24 V AC/DC
Tolerance range: ±10%
See -> signal displays
- Check the connections of the corresponding sensors
(squeezed or brittle supply lines, etc.)
- Check signal sensor *
- Check the connections of the corresponding sensors
(squeezed or brittle supply lines, etc.)
- Check sensor *
Carry out manual reset