Menu level Parameterization level
Zero point tranquilization, ZErO:
ZErO
With zero point tranquilization, a value range around zero can
be preselected at which the display shows zero. If, for
example, a 10 is set, the display would show a zero in the
range from -10 to +10 and continue below it with -11 and
above it with +11.
MIN/MAX value inquiry - Assignment of key functions,
tAST:
tASt
Here, you can enter for the operating mode either a MIN/MAX
value inquiry or a threshold value correction on the arrow
keys.
If the MIN/MAX memory is activated with EHEr, the
measured MIN/MAX values will be saved during operation
and can be called up via the arrow keys [▲] [▼]. The values
are lost if the device is restarted.
If the threshold value correction LI.1 is selected, the limit
values can be changed during operation without hindering the
operating procedure.
If no is parameterized, the arrow keys [▼] [▲] have no
function in operating mode.
Flashing of display, FLAS:
FLAS
Here, flashing of the display can be added as an extra alarm
function, either to the first limit value (select: LI-1), the second
limit value (select: LI-2) or to both limit values (select: LI.12).
With no (works setting), no flashing is assigned at all.
22
0
0
EHEr
LI.12
LI-1
LI-2
WIKA Betriebsanleitung Digitalanzeige Typ DI10
no
LI.12
no