Optical interfaces
Optical inputs
Optical connectors
Data flow indication
Wave length
Launched power
Sensitivity
Optical budget
Maximum distance spanned
Elektronic Output Relais K2
Connections
Switching DC-voltage range
Min. switching current
Max. load current
Max. switching power
Binary Input BI2
Connections
Input voltage range
Pickup voltage of BI2
Pickup voltage of BI2
Input current
Pickup time
Delay time from input to output
Optical input R1 -> X1 (PIN 1/3)
Optical input R2 -> X1 (PIN 4/8)
Optical input R2 -> Electronic relay K2
Binary input BI2 -> X1 (electrical outputs)
Binary input BI2 -> Electronic relay K2
62 / 68
2 receivers
Factory setting: Light OFF in idle state
BFOC connectors (plastic protective caps)
2 X yellow LED (data transfer)
820 nm
-19dBm
with 50/125µm
multimode fibre
-15dBm
with 62,5/125µm
multimode fibre
-30dBm
10dB (+3 dB system budget-safety margin)
1.5 km in combination with SIPROTEC systems
with 62,5/125µm multimode fibre
3.5 m with 980/1000 plastic-fibre
2-pol. Terminal X6
24 – 250V DC +15% -20%
1 mA
100 mA
maximum 250 mW mean power losses,
(Please consider the switching frequency)
2-pol. terminal X5
24 – 250V DC +15% -20%
approx. 17 V DC (with jumper X100 1-2)
approx. 70 V DC (with jumper X100 2-3)
< 5 mA
approx. 5 ms
< 1 µs *
< 1 µs *
< 4 ms
approx. 5 ms
approx. 10 ms
* Up to >1 mA only by closing of the
semiconductor output Up to > 30 mA also when
semiconductor output opens
7XV5654-0BA00
C53000-B1174-C168-2