Connections

WARNING: Danger to life by electric shock
!
Never carry out work when voltage is present.
The operation of the measurement module is only permitted with the mounted devices
!
specified in chapter 4.

7.1 Main connection and line protection

When making the mandatory 3-phase connection, it is essential to observe the terminal
identification.
The control supply voltage and control voltage inputs must be operated with power
supply modules according to IEC 61131-2 (max. 5 % residual ripple).
In order to avoid inductive or capacitive coupling of noise emissions, the use of shielded
conductors is recommended.
The load circuits of the device do not have fuses!

7.2 Mounting

Snap the electronic measurement module onto the CrossBoard® and make sure, the snap
hooks on the back lock safely and firmly. (Image 4)
Image 4
Mounting of the CrossMT onto the CrossBoard
Page 35 of 53
36 400 000 A
English.
Revision 05/2023