Where to install a smoke alarm in rooms with special geometries

• Corridors with a maximum width of 3m: Max. 15m between 2 smoke alarms. Max. 7,5m to the
front side of the gallery and smoke alarms at edges/crossings of corridors.
• Rooms with sloping ceilings:
- If the ceiling inclination is > 20° to the horizontal: Smoke alarms must be installed at least 0.5 m
and at most 1 m from ceiling top.
- Partial roof slopes: If the flat ceiling is ≤ 1m wide, consider as ceiling inclination is of > 20°. If the
flat ceiling is >1m wide, consider as flat ceiling.
• Rooms with subdivided ceilings:
- Height of the subdivisions is ≤ 0.2 m: Beams without consideration; smoke alarm may be installed
on the beams as well as on ceiling.
- Height of subdivisions is > 0.2 m and area of ceiling panels > 36 m²: Smoke alarm should be
installed in each ceiling panel.
- Height of subdivisions > 0.2 m and area of ceiling panels ≤ 36 m²: Individual ceiling without
consideration.
Where not to install a smoke alarm
• In an environment with a high risk of draught (e.g., close to air conditioning, fans and ventilation
outlets). The movement of air can impair the penetration of fire smoke into the smoke alarm.
• Areas where combustions regularly occur, such as kitchens.
• Areas with high humidity such as bathrooms, or close to devices such as dish washers or washing
machines.
Activation
(view page 1_A-B)
• Before using the smoke detector, it is important to activate and test it.
• Use a screwdriver to push the activation switch to "B = ON", on the front side a red LED will light
up very briefly.
• Test the correct activation of your smoke detector by pressing the test button for a few seconds,
you will hear the test signal, the smoke detector is functioning as it should.
• Then return the switch to the "A" position.
• The smoke detector is automatically reactivated by placing it on the mounting plate and turning it
to the left, 2 plastic hooks on the mounting plate set the switch to the "B = ON" position.
Warning
- Replace 10 years after activation: _ _ - _ _ - _ _ _ _
- If the test signal is not heard, the smoke detector must not be used!
Connect your smoke alarms
1. Choose one smoke alarm as the master smoke alarm.
2. Turn your master smoke alarm into the connect mode by quickly pressing the test button 3 times.
3. The red LED (frontside) will light up, followed by the blue LED (backside). This indicates that the
smoke alarm turned into the connect mode in which it remains for 30 seconds.
4. Turn the next smoke alarm into the learn mode by quickly pressing the test button 3 times.
5. The red LED (frontside) will light up, followed by the green LED (backside). This indicates that the
smoke alarms are connected to each other.
6. Repeat step 1 to 5 for connecting more smoke alarms. Make sure that you always use the same
master smoke alarm!