Digitaler Stellungsregler
Digital positioner
Positionneur digital
Manual Limit Setting: (Go Man)
a
Pay attention for actuators with variable acting speed.
In any case, the positioner must be initialized with the effective speed of the actuator with which it is to operate later.
If this is not observed, during operation the controller can switch to the "Target Position Error" state.
+
pls. note: By using the Manual Limit Setting Function, the user must ensure that the Close Tight Functions
is disabled, otherwise a positioning error will be occurred, caused by over traveling the actuator limits. (up/down)
The user must move the valve first to the fully open position (by D and I key switches), confirm (by A/M key switch)
to store the position, then the same for the full close position. On the full close position confirm (by A/M key switch),
the automatic procedure to evaluate the characteristic of the valve is started.
On completion of the procedure the result is prompted to the user (Success or Failure) and the device waits for
users acknowledge; pressing the A/M key switch the unit stores the new calibration data and exits to the normal
operation mode if the procedure was successful, or back to the first step of the procedure.
a
Anytime long press (more than 4 sec) of the A/M key switch aborts the procedure and exits to the
normal operation mode: no new data is stored.
06.12.2022
EBA REpos 8010_de _en_fr 2.0rev1.docx