20.4

Configuration parameter

#
Display
1
Ainp
Analog Input
2
SpRv
Setpoint Inversion
3
Aout
Analog Output Type
4
Rinv
Feedback signal Inversion
5
SplM
Split range mode
6
SplT
Split range Threshold
7
Di1F
Digital Input 1 Function
8
Safe
Safety Position
9
FPos
Safety Position Value
10
Do.F
Digital Output
11
DBnd
Dead band
12
ClTe
Close Tight Enable
13
ClTB
Close Tight Band
06.12.2022
EBA REpos 8010_de _en_fr 2.0rev1.docx
Configuration parameter
Description
Value
0-20mA
4-20mA
0-10V
2-10V
Dir
(direct)
Rev
(invers)
0-20mA
4-20mA
0-10V
2-10V
Dir
(direct)
Rev
(invers)
None
High
Low
20...80%
None
Safe
FPos
Off
Open
Close
0..100%
None
Error
Manual
Remote
0.5...5.0%
En
(aktiv)
Dis
(inactiv)
0.5..5.0%
Technical changes reserved / Modifications techniques sous réserve
Technische Änderungen vorbehalten /
REpos
-8010
Value
Factory reset
4-20mA
Setpoint Input type current/ voltage
Dir
Changes the direction of the setpoint e.g.
(direct)
4mA actuator spindle extended
4mA actuator retraced
4-20mA
Select feedback signal output type
Dir
Changes the direction of the feedback signal
(direct)
e.g.
4mA actuator spindle extended or
4mA actuator retraced
None
Split Range Start area
50%
Split point
None
Target position if Di1 is active
Warning! Di1 has priority over
Safe function.
Off
Actuator position in error mode
e.g., Input signal fault.......
0.0
Setpoint value when Di1F is active
None
Function Digital Output
neutral Zone between operation commands
Auto
open ->close or close->open
En
(aktiv)
Close Tight Function enabling
Auto
Close Tight value for open /close limits
Function