Herunterladen Inhalt Inhalt Diese Seite drucken

ABB FIO-11 Kurzanleitung Seite 3

Analog i/o extension
Vorschau ausblenden Andere Handbücher für FIO-11:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

• Insert the module carefully into the option slot of the drive until
the retaining clips lock the module into position.
• Fasten the screw (included) to the stand-off.
Note: Correct installation of the screw is essential for fulfilling the
EMC requirements and for proper operation of the module.
Terminal designations
Marking
X71, X72, X73
1
2
X74
1
2
X75, X76
1
2
Wiring
Maximum 2.5 mm
cable shields should be connected to the JCU-01 Control Unit.
See the drive Hardware Manual for more information.
Note: Do not route signal cables parallel to power cables.
Tightening torque is 0.5 Nm (4.4 lbf·in.) for the plugs.
Programming
The communication between the module and the drive is activated
by a drive parameter. See the drive Firmware Manual.
Description
Analog input
• Current input -20...20 mA
AIx+
• Voltage input -10...10 V
AIx-
AO1+
Analog output
• Current output: 0...20 mA
AO1-
DIOx
Digital input/output
• 24 V logic levels for input: "0" < 5 V, "1" > 15 V
COM
• Output current 50 mA source, 50 mA sink
2
cable should be used for the signals. The
Quick guide - FIO-11
3

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis