MD 9273 Leakage Clamp
Current Harmonics
N: harmonic component 2 ÷ 9
Measuring range
IhN < 10 % IRange
10 % IRange < IhN < 100 % IRange
N: harmonic component 10 ÷ 19
Measuring range
IhN < 10 % IRange
10 % IRange < IhN < 100 % IRange
IRange:
Nominal clamp current (RMS)
IhN:
measured current magnitude of N
N:
harmonic component
Note: current harmonics are measured at voltages higher than 10% of the range or 0.3 A, whichever is higher.
Note: if Irange is in the 100 A current range, the accuracy of the current harmonics is indicative.
Voltage Harmonics
N: harmonic component 2 ÷ 9
Measuring range:
UhN < 3 % URange
3 % URange < UhN < 20 % URange
N: harmonic component 10 ÷ 19
Measuring range:
UhN < 3 % URange
3 % URange < UhN < 20 % URange
URange:
Voltage range (RMS)
UhN:
measured voltage of Nth harmonic component
N:
harmonic component

Crest Factor

Function
Range
mA, A, V
1.00 ... 2.99
3.00 ... 9.99
NOTE: minimum input signal amplitude is 2 V or 10 mA.
th
Accuracy
± 0.15 % × Irange ± 3 digits
± 1.5 % × IhN ± 3 digits
th
Accuracy
± 0.3 % × Irange ± 3 digits
± 3 % × IhN ± 3 digits
harmonic component
th
th
Accuracy:
± 0.1 % × Urange ± 2 digits
± 1 % × UhN ± 2 digits
th
Accuracy:
± 0.2 % × Urange ± 2 digits
± 2 % × UhN ± 2 digits
Resolution
0.01
0.01
25
Technical Specifications
Accuracy
± 2 % of reading ± 2 digits
± 3 % of reading ± 5 digits