Technical Data - Sauter EGQ110F931 Bedienungs- Und Montageanleitung

Kanal-luftqualitätsfühler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

G
EGQ110F931
Maintenance-free duct sensor with active output, automatic calibration, in a compact plastic housing with snap-on lid, for determining the air quality
(0...100 % VOC). The measuring transducer converts the measured values into a standard signal of 0 -10 V.
The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables
energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.
The air quality is detected by a VOC sensor (mixed gas sensor for volatile organic substances). This sensor determines the loading of the room air
due to contaminated gases such as cigarette smoke, body perspiration, exhaled breathing air, solvent vapours, emissions etc. With regard to the
expected air contamination, low, medium or high VOC sensitivity can be selected.

TECHNICAL DATA

Power supply:
Power consumption:
Sensor:
Measuring range:
Output:
Relay output:
Measuring accuracy:
Service life:
Gas exchange:
Warm-up time:
Response time:
Ambient temperature:
Electrical connection:
Housing:
Housing dimensions:
Cable connection:
Protective tube:
Process connection:
Protection class:
Protection type:
Standards:
Type ⁄ Code
EGQ110F931
Note:
24 V AC ⁄ DC (± 10 %)
< 1.5 W ⁄ 24 V DC typical;
< 2.9 VA ⁄ 24 V AC typical; peak current 200 mA
VOC sensor (metal oxide) (VOC = volatile organic compounds),
with manual calibration (via zero button),
with automatic calibration (permanently active)
0...100 % air quality; referred to calibrating gas;
multi-range switching (selectable via DIP switches)
VOC sensitivities (low/medium/high)
(0 V = clean air, 10 V = polluted air)
0 -10 V or 4...20 mA, working resistance < 800 Ω (selectable via DIP switches)
with offset potentiometer (± 10 % of the measuring range)
with potential-free changeover contact (24 V / 1 A),
switchpoint adjustable
typically ± 20 % of final value (referred to calibrating gas)
> 60 months (under normal load conditions),
depending on the type of loading and gas concentration
by diffusion
approx. 1 hour
approx. 1 minute, minimum flow rate 0.3 m / s (air)
–10...+60 °C
2
0.14 - 1.5 mm
, via terminals
plastic, UV-resistant, material polyamide, 30 % glass-globe-reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination)
colour traffic white (similar to RAL 9016),
72 x 64 x 37.8 mm
cable gland, plastic
(M 16 x 1.5; exchangeable, max. inner diameter 10.4 mm)
material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 202.5 mm, v
max
by mounting flange, plastic (included in the scope of delivery)
III (according to EN 60 730)
IP 65 (according to EN 60 529) Housing with closed cover (protective tube: IP 30)
Housing tested, TÜV SÜD, Report No. 713139052
CE conformity, electromagnetic compatibility according to EN 61 326,
EMC Directive 2014 ⁄ 30 ⁄ EU
Measuring Range
Output
VOC
VOC (switchable)
0...100 %
0 -10 V ⁄ 4...20 mA
This unit must not be used as safety-relevant device!
= 30 m/s (air)
Equipment 
changeover contact
8
Rev. 2021 - V35