Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - Sauter EGQ212F931 Bedienungs- Und Montageanleitung

Multifunktionaler kanalfühler mit messumformer für temperatur und co2-gehalt, selbstkalibrierend, inkl. montageflansch, mit aktivem ausgang
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

G
EGQ212F931
Maintenance-free duct sensor with active output, automatic calibration, in an impact-resistant plastic housing with quick-locking screws, for deter-
mining the CO2 content of the air (0...2000 ppm/0...5000 ppm) and the temperature (–35...+80 °C). The measuring transducer converts the meas-
ured values into a standard signal of 0 -10 V.
The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables
energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being. One sensor for every 30 m²  of
space is recommended.
A digital temperature sensor guarantees exact measurement results. The CO2 measurement is performed using an optical NDIR sensor (non-
dispersive infra-red technology). The detection range is calibrated for standard applications such as monitoring residential rooms and conference
rooms.

TECHNICAL DATA

Voltage supply:
Power consumption:
TEMPERATURE
Sensor:
Sensor protection:
Measuring range, temperature:
Operating range, temperature:
Temperature deviation:
Output, temperature:
CARBON DIOXIDE (CO2)
Sensor, CO2:
Measuring range, CO2:
Output, CO2:
Measuring accuracy, CO2:
Temperature dependence, CO2:
Pressure dependence:
Long-term stability:
Gas exchange:
Ambient temperature:
Response time:
Electrical connection:
Housing:
Housing dimensions:
Cable connection:
Protective tube:
Process connection:
Protection class:
Protection type:
Standards:
Type ⁄ Code
EGQ212F931
Note:
24 V AC ⁄ DC (± 10 %)
< 4.8 W ⁄ 24 V DC typical;
< 6.8 VA ⁄ 24 V AC typical; peak current 200 mA
digital temperature sensor,
low hysteresis, high long-term stability
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
–35...+80 °C
–10...+60 °C
typically ± 0.2 K at +25 °C
0 -10 V
optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button),
with automatic calibration (fixed)
0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
0 -10 V
typically ± 30 ppm ± 3 % of measured value
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C (whichever is higher)
± 0.13 % ⁄ mm Hg
< 2 % in 15 years
by diffusion
–10...+60 °C
< 2 minutes, minimum flow rate 0.3 m / s (air)
2
0.14 - 1.5 mm
, via screw terminals
plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced, 
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016)
126 x 90 x 50 mm
cable gland, plastic
(M 16 x 1.5; exchangeable, max. inner diameter 10.4 mm)
material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 235 mm, v
max
via flange made of plastic (included in scope of delivery)
III (according to EN 60 730)
IP 65 (according to EN 60 529) Housing with closed cover (protective tube: IP 30)
Housing tested, TÜV SÜD, Report No. 713139052
CE conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
Measuring Range
Temperature
CO2 (switchable)
–35...+80 °C
0...2000 ppm /
0...5000 ppm
This unit must not be used as safety-relevant device!
= 30 m/s (air)
Output
Temperature
0 -10 V
8
Rev. 2021 - V33
CO2
0 -10 V

Werbung

Inhaltsverzeichnis
loading