Technical Data - Sauter EGH130F931 Bedienungs- Und Montageanleitung

Raum-feuchte- und temperaturfühler, aufputz, kalibrierfähig, mit aktivem ausgang
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

G
EGH130F931
The calibratable room humidity and temperature sensor measures the relative humidity and/or temperature of air. It converts the measurands
humidity and temperature into standard signals of 0 -10 V and is available in an elegant housing made of plastic, with snap-on lid, base with 4-hole
attachment for installation on vertically or horizontally installed in-wall flush boxes, with predetermined breaking point for on-wall cable entry. The
relative humidity (in % r.H.) is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas tem-
perature.
It is used in non-aggressive dust-free atmospheres in refrigeration, air conditioning, ventilation and clean room technology, in interior rooms such as
residential rooms, offices, hotels, technical rooms, meeting rooms and convention centres. These measuring transducers are designed for exact
detection of air temperature and humidity. A digital long-term stable sensor is used as a measuring element for humidity and temperature measure-
ment. Fine adjustment by the user is possible.

TECHNICAL DATA

Power supply:
Load resistance:
Power consumption:
Sensors:
HUMIDIT Y
Measuring range, humidity:
Operating range, humidity:
Deviation, humidity:
Output, humidity:
TEMPERATURE
Measuring range, temperature: 0...+ 50 °C
Operating range, temperature: 0...+ 50 °C
Deviation, temperature:
Output, temperature:
Ambient temperature:
Electrical connection:
Housing:
Housing dimensions:
Installation:
Long-term stability:
Protection class:
Protection type:
Standards:
Type ⁄ Code
EGH130F931
24 V AC (± 20 %) and 15...36 V DC
R
> 5 kOhm
L
< 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
digital humidity sensor with integrated temperature sensor,
small hysteresis, high long-term stability
0...100 % r. H.
0 ... 95 % r. H. (non-precipitating air)
typically ± 2.0 % (20...80 % r. H.) at +25 °C, otherwise ± 3.0 %
0 -10 V
typically ± 0.2 K at +25 °C
0 -10 V
storage –25...+50 °C,
operation –5...+55 °C
4-wire connection (see connecting diagram)
0.14 -1.5 mm ² via terminal screws
plastic, material ABS,
colour pure white (similar to RAL 9010)
85 x 85 x 27 mm
wall mounting or on in-wall flush box Ø 55 mm,
base with 4-hole for cable entry from the back
±1 % per year
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE conformity, according to EMC directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
Measuring range
humidity
temperature
0...100 % r. H.
0...+50 °C
Output
humidity
0 - 10 V
7
Rev. 2021 - V23
temperature
0 - 10 V