Connecting scheme
Power supply
AC 24V~
0V
DC 15-36V = GND
SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or
reverse polarity protection diode is integrated in this device variant.
This internal one-way rectifier also allows operating 0 - 10 V devices on AC
supply voltage.
The output signal is to be tapped by a measuring instrument. Output
voltage is measured her against zero potential (O V) of the input voltage!
When this device is operated on DC supply voltage , the operating voltage
input UB+ is to be used for 15...36 V DC supply and UB – or GND for
ground wire!
Schematic diagram
Zero
OFFSET
SET
13 11 12 1 2 3
Connecting diagram
1
UB+ 24V AC/DC
2
Output air quality 0-10 V / 4...20mA
3
UB– GND
Breaker
12
11
Normally
open contact
13
Individual operation
Circuitry
V
EGQ110F931
ON DIP
1 2 3 4
EGQ110F931
changeover
24V/1A
Connecting scheme
Power supply
AC 24V~
0V
DC 15-36V = GND
When several devices are supplied by one 24 V AC voltage supply, it is to
be ensured that all "positive" operating voltage input terminals (+) of the
field devices are connected with each other and all "negative" operating
voltage input terminals (–) (= reference potential) are connected together
(in-phase connection of field devices). All outputs of field devices must be
referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short-
circuit would be caused by that device. The consequential short-circuit
current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!
DIP switches
VOC sensitivity
LOW
MEDIUM (default)
HIGH
IAQ (Indoor Air Quality)
Output
Voltage 0 -10 V (default)
Current 4...20 mA
Note: DIP 3 is not assigned!
Level
IAQ (Indoor Air Quality)
1
excellent
no action required
2
good
prompt airing recommended
3
moderate
airing recommended
4
poor
increased airing required
5
unhealthy
intense airing necessary
Table according to TVOC guidelines of the German Federal
Environmental Agency to assess indoor air contamination
(Bundesgesundheitsbl - Gesundheitsforsch -
Gesundheitsschutz 2007, 50: 990–1005)
10
Rev. 2021 - V35
Parallel operation
Circuitry
Circuitry
DIP 1
OFF
O N
OFF
O N
DIP 4
0...19 %
20...39 %
40...59 %
60...79 %
80...100 %
DIP 2
OFF
OFF
O N
O N
OFF
O N
VOC