Programming via teach cable
→ Set the linear actuator to the "closed"
position.
→ If you have not already done so, disconnect
the M12 cable from the position indicator plug
and connect it to the 4-pin side of the teach
cable.
→ Now connect the teach cable to the position
indicator to restore the power supply.
→ The LEDs start flashing purple.
→ Now press the button of the teach cable for 1
to 2 seconds to enter the programming mode.
→ The LEDs are now permanently purple and the
programming mode has been activated.
→ If it is a two-stage actuator, move it to the
middle position. If the point has been taught in
successfully, the LEDs will flash green-violet as
confirmation.
→ Move the actuator to the "open" position. If
the point has been taught in successfully, the
LEDs flash green-violet as confirmation.
→ Move the actuator to the "closed" position. If
the point has been taught in successfully, the
LEDs flash orange-violet and afterwards
continuously blue.
© 1994 - 2022 SED Flow Control
Move valve to closed
position
Connect connection cable
with teach-in cable
Connect teach-in cable with
024.50
Press the button on the
teach-in cable.
Trigger signal approx. 2sec
Display lights up
purple
Open valve
Display flashes green-
violet.On top position
display changes from green-
violet flashing to continuous
mode violet.
Close actuator. Display
flashes violet-orange in
closed position, then
permanently blue
Programming completed
30
2-stage
actuator
Move valve to middle
position, LEDs flash green-
violet
In the middle
position, LEDs light
up violet