Herunterladen Inhalt Inhalt Diese Seite drucken

Samson 024.50 Originalbetriebsanleitung Seite 57

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Original Betriebsanleitung
Typ 024.50
Name
Description
DetailedDeviceStatus
Detailed device status
Detailed device status [1]
Detailed device status [2]
Detailed device status [3]
Detailed device status [4]
ProcessDataInput
ProcessDataOutput
NormalMode
Change normal mode
Settings
Settings
Bit 0: Reserved for future
functions
Bit 1: Inversion of feedback
signals
Bit 2: Reserved for future
functions
Bit 3: Reserved for future
functions
Bit 4: On site programming
Bit 5: Reserved for future
functions
Bit 6: Reserved for future
functions
Bit 7: warning undefinde
position active
Switch point MIDDLE
SwitchPoint_close
SwitchPoint_middle
Schaltpunkt MITTE
© 1994 - 2022 SED Flow Control
Index
Sub index/
Data type
Bit offset
37
0 / 0
ArrayT
1 / 216
OctetStringT
2 / 192
OctetStringT
3 / 168
OctetStringT
4 / 144
OctetStringT
40
0 / 0
UIntegerT
41
0 / 0
UIntegerT
79
0 / 0
UIntegerT
80
0 / 0
UIntegerT
1 / 0
BooleanT
2 / 1
BooleanT
3 / 2
BooleanT
4 / 3
BooleanT
5 / 4
BooleanT
6 / 5
BooleanT
7 / 6
BooleanT
8/7
BooleanT
81
0 / 0
UIntegerT
82
0 / 0
UIntegerT
15
BA_024.50_v03 Version: a
length
Access
default
12 Byte
RO
3 Byte
3 Byte
3 Byte
3 Byte
8 Bit
RO
8 Bit
WO
8 Bit
RW
0
8 Bit
RW
1 Bit
RW
0 (off/false)
1 Bit
RW
0 (off/false)
1 Bit
RW
0 (off/false)
1 Bit
RW
0 (off/false)
1 Bit
RW
1 (on/true)
1 Bit
RW
0 (off/false)
1 Bit
RW
0 (off/false)
1 Bit
RW
0 (off/false)
8 Bit
RW
25
8 Bit
RW
12
Value range
Factor
Unit
0 .. 2
0 (off/false)
1 (on/true)
0 (off/false)
1 (on/true)
0 (off/false)
1 (on/true)
0 (off/false)
1 (on/true)
0 (off/false)
1 (on/true)
0 (off/false)
1 (on/true)
0 (off/false)
1 (on/true)
0 (off/false)
1 (on/true)
3 .. 97
%
3 .. 97