Programming via pin 5
→ Set the linear actuator to the "closed"
position.
→ If not already done, screw on 5-pin M12
connector with voltage supply.
→ The LEDs start flashing purple.
→ Now apply a voltage signal with 24V DC for 1
to 2 seconds to pin 5 of the M12 connector to
enter the programming mode.
→ The LEDs are now permanently purple and the
programming mode has been activated.
→ If it is a two-stage actuator, move it to the
middle position. If the point has been taught in
successfully, the LEDs will flash green-violet as
confirmation.
→ Move the actuator to the "open" position. If
the point has been taught in successfully, the
LEDs flash green-violet as confirmation.
→ Move the actuator to the "closed" position. If
the point has been taught in successfully, the
LEDs flash orange-violet and afterwards
continuously blue.
© 1994 - 2022 SED Flow Control
Move valve to closed
position
Screw on 5-pin connector
Display flashes
purple for 20
seconds
Apply voltage to pin 5.
Trigger signal for approx.
2sec
Display lights up
purple
2-stage
actuator
Open valve
Display flashes green-violet.
At top position, display
changes from green-violet
flashing to continuous mode
violet.
Close actuator,display
flashes violet-orange in
closed position, then lights
up permanently blue
Programming completed
29
Move valve to middle
position, LEDs flash green-
violet
In the center
position, LEDS
light up violet
BA_024.50_v03 Version: a