Summary of field settings
Mode
First
No.
code
(Note 1)
No. Description of setting
Filter contamination
- Heavy/Light
= Setting to define
time between 2 filter
cleaning display
indications. (When
Long-life
0
contamination is
filter
high, setting can be
changed to half the
time inbetween 2
filter cleaning
display indications.)
2
Thermostat sensor selection
10
(20)
Setting for display of time
3
between 2 filter cleaning display
indications
Information to I-manager,
5
I-touch controller
Thermostat sensor in group
6
control
Output signal X1-X2 of the
0
optional KRP1B PCB kit
ON/OFF input from outside
(T1/T2 input) = Setting when
1
forced ON/OFF is to be
operated from outside.
Thermostat differential
12
2
changeover = Setting when
(22)
remote sensor is used.
Fan setting during thermostat
3
OFF at heating operation
Differential automatic
4
changeover
5
Auto-restart after power failure
Setting for air outlet
other
velocity
models
0
This setting is to be
FMCQ125
changed in function
only
of ceiling height.
Selection for air flow direction
13
This setting is to be changed
1
(23)
when blocking pad optional kit
is used.
Airflow direction range setting
This setting is to be changed
4
when range of swing flap
movement needs to be
changed.
Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected,
indoor units can also be set individually.
Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 : If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01,
10-2-02 or 10-2-03 have priority.
Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have priority.
Note 7 : More settings for Differential automatic change over temperatures are:
Second code No.
05
4°C
06
5°C
07
6°C
08
7°C
When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.
FMCQ50~125A7VEB
Air conditioning system
4PW47629-1
Second code No. (Note 2)
01
02
03
±2,500 hrs.
±1,250 hrs.
Use both the
unit sensor (or
Use unit sensor
remote sensor if
Use remote
only (or remote
installed) AND
controller
sensor if
the remote
sensor only.
installed).
controller
(See note 5+6)
(See note 5+6)
sensor.
(See note 5+6)
Display
Do not display
Only unit sensor
Sensor value as
value (or remote
set by 10-2-0X
sensor value if
or 10-6-0X.
installed).
Use both the
unit senor (or
Use unit sensor
remote sensor if
only (or remote
installed) AND
sensor if
the remote
installed).
controller
(See note 6)
sensor. (See
note 4+5+6)
Thermostat-on +
Mal-
Operation
compressor run
function
ON/OFF
Forced OFF
operation
1°C
0.5°C
OFF
LL
Set speed
(See note 3)
3°C
0°C
1°C
2°C
(See
note 7)
Disabled
Enabled
≤2.7 m
>2.7 ≤3.0 m
>3.0 ≤3.5 m
≤3.2 m
>3.2 ≤3.6 m
>3.6 ≤4.2 m
4-way flow
3-way flow
2-way flow
Upper
Medium
Lower
Control by 2 Remote Controllers (Controlling 1 indoor
unit by 2 remote controllers)
When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".
04
Main/sub changeover
1.
Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. (See figure 18)
(The remote controller PC board is attached to the upper part of
the remote controller.)
2.
Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". (See figure 19)
(Leave the switch of the other remote controller set to "M".)
1
Remote controller PC board
2
Factory setting
3
Only one remote controller needs to be changed
Computerised control (forced off and on/off operation)
1.
Wire specifications and how to perform wiring.
Connect input from outside to terminals T1 and T2 of the terminal
block (remote controller to transmission wiring).
Wire specification
Gauge
Length
Contact that can ensure the minimum applicable load
External terminal
See figure 17.
1
Input A
2.
Actuation
The following table explains "forced off" and "on/off operations" in
response to input A.
Forced off
Input "on" stops operation
Input "off" enables control
3.
How to select forced off and on/off operation
Turn the power on and then use the remote controller to select
operation.
Set the remote controller to the field set mode. For details, refer to
the chapter "How to set in the field", in the remote controller
manual.
When in the field set mode, select mode No. 12, then set the first
code (switch) No. to "1". Then set second code (position) No. to
"01" for forced off and to "02" for on/off operation. (forced off at
factory set.) (See figure 16)
1
Second code No.
2
Mode No.
3
First code No.
4
Field set mode
Centralized control
For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.
Sheathed vinyl cord or cable (2 wire)
2
0.75-1.25 mm
Max. 100 m
of 15 V DC, 1 mA
on/off operation
input off
on: turns on the unit
(impossible by remote controllers)
input on
off: turns off the unit
(by remote controller)
Installation and operation manual
8