UNITS INSTALLATION
Service Access Panel
Provide a service access door or panel as shown below.
Unit (inside)
Floor
Service access
panel
(Space around Indoor Unit) (mm)
Model
A
RPF
1.0
1.5
630
2.0
2.5
Consider the air distribution from the indoor unit to the space
of the room, and select a suitable location so that uniform air
temperature in the room can be obtained.
Check to ensure that the foundation is flat, level and
sufficiently strong.
It is recommended that a service access panel for floor
concealed type indoor units be provided. The access panel
must be fixed with screw(s) so that service engineer(s) only
is accessible.
3.1.3 Installation
1 Check to ensure the fixing position of the unit as shown
below.
Fixing onto floor using wood
screws (2-M8) (View from top side)
Fixing onto floor using wood
screws (4-M5) (View from top side)
Model
A
B
RPF-1.0
1045
754
RPF-1.5
1170
879
RPFI-1.0
863
754
RPFI-1.5
988
879
RPF-2.0
1420
1129
RPF-2.5
RPFI-2.0
1234
1129
RPFI-2.5
5
PMML0159A rev.3 - 05/2016
Service access
B
panel
Size
B
RPFI
RPF
RPFI
1479
1359
620
1729
1609
Fixing onto wall
(View from front side)
C
D
E
F
732
217
228
140
857
732
66
77
138
857
11
1107
228
140
11
1107
53
139
2 Adjust the flat level of the unit by adjusting bolts for
installation which are attached in the unit. Make the drain
pipe side lower than the opposite side for smooth drain.
3 Fix the base plate and back plate of the unit with field-
supplied fixing bolts and screws. When attaching the
adjusting bolts for installation, remove the electrical wiring
box.
4 In case of the RPF unit, perform the above work after
removing the front cover and side cover of the unit.
Side cover
Fixing bolt
Fixing bolt
5 Install the optional air outlet grille of the RPFI unit as shown
in the following figure. If installed in a comparatively high
humid place, condensation may occur. Therefore, attach a
plate which can absorb water, like SUNKEN AQ made by
ASAHI Chemical Co., around the grille.
Air outlet
flange
Floor
concealed unit
!
C A U T I O N
Provide a service access cover which is fixed by screws so that the fan
runner is not directly touched (Only RPFI model).
!
C A U T I O N
The optional air outlet grille of the RPFI unit can not be used in a highly
humid place like a kitchen, because condensation may occur on the grille
surface.
(mm)
G
630
620
630
620
Front cover
Adjustment bolt for
installation (accessories)
Fixing screw
Absorbent plate
for water
Ex.: SUNFINE AQ made
by ASAHI Chemical Co.
Polyurethane foam for thermal
insulation (field-supplied)
Air outlet duct
(field-supplied)