58
12. Technical specifications and installation dimensions
12.1 Technical specifications
In order to prevent condensation on the electronic components and
the stator, the liquid temperature must always be higher than the
ambient temperature.
Ambient
temperature (°C)
0
10
20
30
35
40
In domestic hot water systems, it is recommended to keep the liquid
temperature below 65 °C to prevent lime deposits.
GB
Circulation pump for heating and solar
Liquid temperature
minimum (°C)
2
10
20
30
35
40
Highly efficient. Simple. Good!
maximum (°C)
110
110
110
110
90
70