9.Maintenance

• When using the test adapter in compliance with the user manual, no special maintenance is required.
• However, should functional errors occur during normal operation, the after sales service will repair your instrument.
• Please contact the local service office.

9-1.Cleaning

• If the test adapter needs to be cleaned after daily usage, use a wet cloth and a mild household detergent.
• Prior to cleaning, disconnect the test adapter from all measurement circuits.
• Never use acid-based detergents or dissolvent liquids for cleaning.
• After cleaning, do not use the test adapter until it is dried completely.

9-2.Transport and Storage

• Please keep the original packaging for future transport(e.g.,if calibration is necessary), any transport damage
due to faulty packaging will be excluded from warranty claims.
• The adapter must be shored in dry, closed areas.
• In case of an adapter being transported in extreme temperatures, a minimum recovery time of 2 hours is required
prior to any operation.

9-3.Fuse Replacement

• The fuse (10A (H)/250V, 5x20mm) may be blown if no voltage is present between the L and N terminals of mains
socket when the charging connector is connected to the charging station and the charging station is in charging
mode.
• If a fuse blows (due to overload or improper operation),follow the steps below for replacement:
1.Unscrew the fuse holder cap using an appropriate screwdriver.
2.Remove the defective fuse and replace it with a new one.
3.Replace the fuse holder cap.
If the fuse blows several times the adapter must be sent to the service department in order to be checked.
Use only fuses as defined in technical specification, using alternative fuses may create a safety risk!
34