Herunterladen Inhalt Inhalt Diese Seite drucken

Testing Charging Stations; 8-1.Purpose Of The Test Adapter - Uniks EV CHECK Benutzerhandbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

EV CHECK
Test Cable Input
13-
CP Signal Output Terminal
14-
CP Signal Output Terminal (Connected to PE)
15-
Fuse 10A/250V, 5x20mm Protects Mains Socket Against Overload
16-

Testing Charging Stations

8.

8-1.Purpose of the Test Adapter

There are two main purposes of the Test Adapter:
To simulate connection of an electrical vehicle to the tested charging station (the test adapter simulates electrical
1.
vehicle and charging cable), connection of the test adapter to a charging station triggers the charging process in
the charging station (CP switch at the adapter shall be in appropriate mode), various cable charging capabilities
can be simulated (NC,13A,20A,32A and 63A) as well as all possible electrical vehicle modes (A, B,C,D).
To provide easy access to charging terminals L1,L2,L3,N,PE and to CP signal terminals to which additional
2.
measuring equipment can be connected for further testing, charging stations should be tested after installation
and repeated periodically.
Please refer to the manufacturer's recommendation and national standards which are linked to IEC/HD 60364-6
for initial test or IEC/HD 60364-7-722, required tests are:
• Visual inspection
CP Signal Output
28