Herunterladen Diese Seite drucken
Honeywell MI-D240CMOE Installationsanleitung
Honeywell MI-D240CMOE Installationsanleitung

Honeywell MI-D240CMOE Installationsanleitung

Steuermodule für netzschaltspannung

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Fig./Abb. 1
1:2 DIN
1:1 M200E-SMB
Sollevare
Levantar
Anheben
Fig./Abb. 2
Fig./Abb. 3
Note:
In order to meet the requirements of European Safety Standards, ensure
that all cables carrying voltages in excess of 48V are suitably fused.
DOP-IOD085
EN54-17: 2005
EN54-18: 2005
0786
0786
22
M200-502-00
Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ
INSTALLATION INSTRUCTIONS FOR MAINS
SWITCHING OUTPUT MODULE
60°C
-20°C
2
1
Rotate
Plug
Ruotare
Inserire
Girar
Conectar
Drehen
Einhaken
Clip / Agganciare
3
Acoplar / Einrasten
3
1
Lift
Push down
Premere
Precionar
hacia abajo
Runterdrücken
Rotate / Ruotare
2
Girar / Drehen
MI-D240CMOE
Honeywell Morley-IAS
Pittway Tecnologica S.r.l
Via Caboto 19/3
34147 Trieste, Italy
MI-D240CMOE
This manual is intended as a quick reference installation guide. Please
refer to the control panel manufacturers installation manual for detailed
system information.
The installation must be carried out by expert personnel, that is, a person
with education or experience to identify hazards and take appropriate
actions to reduce the risk of injury to themselves and others.
GENERAL INFORMATION
MI-D240CMOE
The Morley series of modules are a family of microprocessor controlled
interface devices permitting the monitoring and/or control of auxiliary
devices. The MI-D240CMOE is an output module, providing 250VAC
5A rated voltage free contacts, both normally open and normally closed.
SPECIFICATIONS
M200E-SMB
Operating Voltage Range:
LED Cutoff Voltage:
Maximum Standby Current (µA): 75µA - No Communication
Fault Current:
Coil Activation/Deactivation Current: 76mA Maximum for 12ms
Relay Contact Rating:
Isolator Features:
Operating Temperature:
Humidity:
Maximum Wire Gauge
Disconnect loop power before installing modules or sensors.
High voltages may be present on terminals 7 to 12.
INSTALLATION
Note: This module must only be connected to control panels using
compatible proprietary analogue addressable communication protocols for
monitoring and control.
Morley series modules can be mounted in several ways (See Figure 1):
1:1 An M200E-SMB custom low profile surface-mounting box. The SMB
Base is affixed to mounting surface, and then the module and cover
are screwed onto the base using the two screws supplied. Box
dimensions: 132 mm (H) x 137 mm (W) x 40 mm (D)
1:2 The DIN bracket on top allows mounting onto standard 35 mm x 7.5
mm "Top Hat" DIN rail inside a control panel or other suitable enclosure.
Install and remove as shown in Figure 1:2.
Wiring to all series Morley modules is via plug in type terminals capable
of supporting conductors up to 2.5 mm²
Ensure that the correct terminals are used for the loop and
switched voltage as damage may result from incorrect usage.
The module address is selected by means of rotary decade address
switches (see figure 3), accessed at the front of the module. A screwdriver
should be used to rotate the wheels to select the desired address. (Note:
The number of addresses available will be dependent on panel capability,
check the panel documentation for information on this).
Short Circuit Isolators
All Morley series modules are provided with short circuit monitoring and
isolators on the intelligent loop. If required the isolators may be wired
out of the loop to facilitate the use of the modules on high current loaded
loops, for example if sounders are used. To achieve this, the loop out
positive should be wired to terminal 4 rather than terminal 2.
E N G L I S H
see S00-7100
16.5 VDC
5.5 mA (Yellow LED illuminated)
5A at 30VDC, 5A at 250VAC
see S00-7100
-20°C to 60°C
5% to 95% Relative Humidity
2.5 mm²
CAUTION
WARNING
I56-4428-000

Werbung

loading

Inhaltszusammenfassung für Honeywell MI-D240CMOE

  • Seite 1 48V are suitably fused. Honeywell Morley-IAS DOP-IOD085 Pittway Tecnologica S.r.l EN54-17: 2005 Via Caboto 19/3 EN54-18: 2005 0786 0786 34147 Trieste, Italy M200-502-00 Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ I56-4428-000...
  • Seite 2 A questo scopo, cablare l'uscita loop positiva al morsetto 4 Honeywell Morley-IAS anziché al morsetto 2. DOP-IOD085 Pittway Tecnologica S.r.l EN54-17: 2005 Via Caboto 19/3 EN54-18: 2005 0786 0786 34147 Trieste, Italy M200-502-00 Honeywell Morley-IAS, 140 Waterside Road, Hamilton Industrial Estate, Leicester, LE5 1TN, UK I56-4428-000...
  • Seite 3 4 en vez de al terminal 2. Honeywell Morley-IAS DOP-IOD085 Pittway Tecnologica S.r.l EN54-17: 2005 Via Caboto 19/3 EN54-18: 2005 0786 0786 34147 Trieste, Italy Honeywell Life Safety Iberia, S.L. C/ Pau Vila, 15-19, 08911 Badalona (Barcelona) Espana M200-502-00 I56-4428-000...
  • Seite 4 -20°C Die Module der Serie Morley sind Mikroprozessor gesteuerte Elemente die die Überwachung und/oder Steuerung von externen Baugruppen ermöglicht. Die Module der Serie MI-D240CMOE verfügen über potentialfreie Ausgänge, mit wahlweiser Schließer/Öffner Funktionalität, über die eine Netzwechselspannung von 250VAC/5A geschaltet werden M200E-SMB kann.