Herunterladen Inhalt Inhalt Diese Seite drucken

Set-Up/Operation - IFM Electronic Efector 150 KNM Bedienungsanleitung

Kapazitiver niveauschalter
Vorschau ausblenden Andere Handbücher für Efector 150 KNM:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

• Adjustment to the empty state outside the operating range (e.g.
adjustment to the empty state with direct contact with an electri-
cally grounded medium, e.g. if the active face is immersed in water).
Help: Avoid the above-mentioned errors and repeat the adjustment.
Further faults:
• Electronic fault or sensing zone of the unit damaged
• Internal fault (can only be deleted by disconnecting and connecting
power again, hardware reset).
6 Set-up / operation
Check the safe functioning of the unit. Display by LEDs.
LED green
LED yellow
LED red
LED yellow and red
The red LED indicates no malfunction of the unit, it indicates that the
internal sensor signal is near the switching threshold.
Two cases can be distinguished:
• Normal operation/safe operation
The red LED is lit temporarily during the change between "medium"
and "no medium".
14
All manuals and user guides at all-guides.com
ON = unit is ready for operation
flashes slowly (1 Hz) = adjustment mode empty state
flashes quickly (2 Hz) = adjustment mode full state
OFF = switching output disabled
ON = switching output enabled
flashes quickly (2 Hz) = error message
ON = undefined operating range
flash quickly simultaneously (2Hz)
= short circuit of the switching output
OFF = locking mode