Terminal Content
The load table is part of the certification label. This table gives you information about
the relation between conductor cross section and current.
Klippon
POK 162609 Ex, IBExU13ATEX1004X, H: 160 mm, W: 260 mm, D: 90 mm
®
Current
(A)
1.5
Maximum number of conductors
6
10
52
15
21
21
28
36
50
66
a) No limits (consider assembly standards)
b) Not allowed (except with manufacturer heat rise calculation)
Example of a load table.
Any changes to the physical terminal content or details relating to the assembled
enclosure configuration may invalidate the approval.
ATEX Terminal & Cross-Connection Arrangements
Cross connections may cause a derating of the voltage and current ratings of the
terminals. These deratings are shown in the content table as a separate line with a
reference to the terminal designation and the cross connection arrangement.
You find a cross connection guide in the appendix or contact Weidmüller for further support.
16
Cross-section
(mm²)
2.5
4
6
a)
40
17
34
16
30
15
b)
10
16
37
13
34
3
13