INDOOR unit terminal blocks
Morsettiere unità INTERNA
(1)L
from the terminal blocks
dalle morsettiere
of the OUTDOOR unit
dell'unità ESTERNA
Magnetic ring
Pass the strap through the
hole in the magnetic ring
to secure it to the cable
20
(2)N
S
Fig. 23
1 2 3
Fig. 24

REMOTE ON-OFF

For the input of the remote control terminal CN23
(ON-OFF) and the JR6 quick-release connector
– Remove the JR6 quick-release connector when
using the ON-OFF function;
– When the remote switch is OFF (OPEN), the unit
will be turned off;
– When the remote switch is ON (CLOSE), the unit
will be turned on;
– When the remote switch is opened/closed, the unit
will respond to the request within 2 seconds;
– When the remote switch is ON, the remote/wired
control can be used to select the mode; when the
remote switch is OFF, the unit will not respond to
the remote/wired control request.
When the remote switch is OFF, the remote/wired
control is on, code CP will be shown on the display
board.
– The input voltage is 12 V DC, the maximum design
current is 5 mA.
ALARM
For the input of ALARM connector CN33
Power
– The terminal input is set up for ALARM connection,
but there is no voltage; the power supply comes
from the ALARM system (not from the unit)
– Although the design voltage can withstand even
higher values, we strongly advise connecting a
power supply of less than 24 V and a current of
less than 0.5 A
– If this problem occurs on the unit, the relay will be
closed, thus activating the ALARM
Installation
Fig. 25
Fig. 26