Adjustment of the valve positions of valves with 3 operating positions
Press the Pos.
1
pushbutton for min. 2s.
Put the valve into the
2
closed Pos. and press
the Teach button.
Put the valve into the
3
position seat lift and
press the Teach button.
Put the valve into the
4
open position and
press the Teach button.
Press the Pos.
pushbutton for
min. 5s.
5
After 5s the LED
"open" flashes at
about 2Hz.
All manuals and user guides at all-guides.com
All LEDs flash 2x simultaneously.
mode.Then only the LED "closed" is lit.
The unit is now ready for the adjustment
The unit has stored the closed position
and is now ready for the adjustment
The unit has stored the position seat lift
and is now ready for the adjustment
and the LED "closed" lights again.
The unit has now stored all positions.
After releasing all stored measured values
are checked. If no errors are detected all
LEDs flash 2x simultaneously. The unit
automatically quits the programming
mode and immediately passes into the
If, however, an error is found during the
check the LED "closed" flashes at about
8Hz. Acknowledge the error message by
pressing the Pos. button and repeat the
The unit is in the programming
of the closed position.
The LED "closed" goes out
and the LED "seat" lights.
of the position seat lift (seat).
The LED "seat" goes out
and the LED "open" lights.
of the open position.
The LED "open" goes out
operating mode.
adjustment.
25