IFM Electronic efector180 IX5010 Bedienungsanleitung Seite 24

Elektronischer ventilhubsensor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Adjustment of the valve positions of valves with 2 operating positions
Press the Pos. pushbut-
1
ton for at least 2s.
Close the valve and
2
press the Teach button.
Press the Pos. button
once, thus skipping the
current program step.
3
This is necessary
because your valve
does not have the
position "seat lift".
Put the valve into the
4
open position and
press the Teach button.
Press the Pos. pushbut-
ton for at least 5s.
5
After 5s the LED
"open" flashes at
about 2 Hz.
24
All manuals and user guides at all-guides.com
All LEDs flash 2x simultaneously.
The unit is in the programming mode.
Then only the LED "closed" is lit.
The unit is now ready for the adjustment
The unit has stored the closed position
and is now ready for the adjustment of
adjustment of the open position.
and the LED "closed" lights again.
The unit has stored all positions now.
After releasing all stored measured values
are checked. If no errors are detected all
LEDs flash 2x simultaneously. The unit
automatically quits the programming
mode and immediately passes into the
If, however, an error is found during the
check the LED "closed" flashes at about
8Hz. Acknowledge the error message by
pressing the Pos. button and repeat the
of the closed position.
The LED "closed" goes out
and the LED "seat" lights.
the position seat lift (seat).
The LED "open" lights.
The unit is now ready for the
The LED "open" goes out
operating mode.
adjustment.