BTL6-A/G301-M_ _ _ _-A1-S115
Magnetostrictive Linear Position Sensor – Profile Style
6
Programming (continued)
6.2
Programming Output 1
BTL6-A/G301... with at least 1 magnet in the measuring range
Enable programming mode
– Enable La = Programming input La at 0 V
– Enable Lb = Programming input Lb at 0 V
► Enable programming input La or Lb until LED
comes on.
BTL is in programming mode
Error message on both outputs (10.5 V).
Select Output 1
► Enable programming input La until LED comes
on continuously.
⇒ Output 1 selected, both outputs again
provide the current position value.
a) Set zero point
1. Place magnet 1 at desired zero point.
2. Enable programming input La until LED comes
on continuously.
⇒ Zero point for Output 1 programmed,
continue with programming mode
b) Set end point
1. Place magnet 1 at desired end point.
2. Enable programming input Lb until LED comes
on continuously.
⇒ Ends point for Output 1 programmed,
continue with programming mode
The programming inputs may only be
connected to Pin 2 (0V), not to Pin 6 (GND)!
12
english
Operating mode
4 s < t <8 s
La
Programming mode
4 s < t <8 s
4 s < t <8 s
Lb
4 s < t <8 s
LED off
LED flashes very
slowly (0.5 s off/0.5 s
on)
/
Lb
La
La
Programming mode
LED on
LED flashes fast (0.05 s
off/0.05 s on)
LED