CONNECTION DIAGRAM

L N
1x230 V

CONNECTIONS

Switch off power before starting work on the equipment.
Recommended tightening torque on terminals 0.5 Nm; max tightening torque 0.8 Nm.
Input voltage
(L-N-PE)
Motor
(U-V-W)
Thermal contact
(T-T)
Alarm relay
(13-14-15)
Input signal
(2-3)
Rotation monitor
(9-10)
Manual speed
(A1-A2)
U V W
T
T
M
3 ~
3 x 230 V
Thermal
contact
1x230-240 V +/-15%, 50/60 Hz.
NOTE! Protective earth must always be connected.
Three-phase induction motor wired for 3x230 V (Delta).
Max 370 W.
Direction of rotation is changed by switching two of the phases.
The thermal contact in the motor should be used to protect the motor
from overheating.
Must be jumped if the temperature switch is not connected.
Closes between 14-15 in the event of an alarm or voltage drop-out.
Max 8 A resistive load / 250 V AC.
0-10 V.
Plus connected to terminal 2, minus to terminal 3.
White cable connected to terminal 9, brown to terminal 10.
The magnet is installed with south side (S) towards the transmitter.
Max. gap 15 mm.
Provides set max rpm when closed, regardless of input signal value.
A1 A2
(Max 8 A/
250 V AC)
Manual
speed
13 14 15
2 3
9 10
+
Alarm
Input
Rotation
relay
signal
monitor
0 -10 V
10
w
S