DIP SWITCH

Cleaning
Rotation monitor
High speed*
Low speed*
*
Manual operation (test mode)

OPERATIONAL INDICATIONS

On/alarm
Run
Rotation
Cleaning function set to ON position.
When the wheel has stopped for 30 minutes, the cleaning function is
activated and the wheel rotates at minimum speed for 10 seconds.
Rotation monitor set to ON position.
The wheel rotates at the set maximum rpm when the switch is set to ON.
After a test run, make sure the DIP switch is set to OFF.
The wheel rotates at the fixed minimum rpm when the switch is set to
ON.
After a test run, make sure the DIP switch is set to OFF.
"Power on" is lit continuously.
It flashes when the control unit has tripped.
Comes on when the motor is to rotate, i.e. when the input signal exceeds
the threshold value.
Flashes when the magnet passes the magnetic sensor, regardless of the
"Rotation monitor" DIP switch setting.
Flashes even if the input signal is lower than the threshold value.