Herunterladen Inhalt Inhalt Diese Seite drucken

Connection Diagram; Connections - IBC control MicroMax180 Handbuch

Steuereinheit für rotierende wärmetauscher
Vorschau ausblenden Andere Handbücher für MicroMax180:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

CONNECTION DIAGRAM

L N
1x 230 V

CONNECTIONS

Switch off power before starting work on the equipment.
Recommended tightening torque on terminals 0.5 Nm; max tightening torque 0.8 Nm.
Input voltage
(L-N-PE)
Motor
(U-V-W)
Thermal contact
(T-T)
Alarm relay
(13-14-15)
Input signal
(2-3)
Rotation monitor
(9-10)
U V W
T
T
1
2
4
5
3
M
3 ~
3 x230 V
Thermal
contact
(Max 8 A/250 V AC)
1x230-240 V +/-10 %, 50/60 Hz.
NOTE! Protective earth must always be connected.
Three-phase induction motor wired for 3x230 V (Delta).
Max 180 W.
Direction of rotation is changed by switching two of the phases.
The thermal contact in the motor should be used to protect the motor
from overheating.
Must be jumped if the temperature switch is not connected.
Closes between 14-15 in the event of an alarm or voltage drop-out.
Max 8 A resistive load / 250 V AC.
0-10 V.
Plus connected to terminal 2, minus to terminal 3.
White cable connected to terminal 9, brown to terminal 10.
The magnet is installed with south side (S) towards the transmitter.
Max. gap 15 mm.
13 14 15
2 3
+
Alarm relay
Input
signal
0 -10 V
10
9 10
br
w
S
Rotation
monitor

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

F21018201

Inhaltsverzeichnis