Herunterladen Diese Seite drucken

Siemens 3NJ6 Betriebsanleitung Seite 15

Steckbare lasttrennleisten mit sicherungen

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Auxiliary switch
3NJ6912..
Electrical design
Cross-sections
16
All manuals and user guides at all-guides.com
Equipment for the main circuit
a
b
Fig 2: Electical design
a Module for fuses of sizes NH 00, 1, 2 and 3
b 3NJ61.0 -.E..1-OBBO
Switch disconnector with fuse element with independent manually operated snap-action
mechanism for DIN fuses; in sizes NH 00, 1, 2 and 3
c 3NJ61.0 -.M..1-OBBO- as b, but with breaking on both sides of the fuses
d Switch disconnector with independent manually operated snap-action mechanism
The following table contains the possible cross-sections for connection with cable lugs and
cable terminals:
Device
size
Screw size
00
M8
1
M12
2
M12
3
M12
c
Cable lug
Torque [Nm]
15
30
30
30
Auxiliary switch terminals of the
plug-on in line-type fuse switches
are located
in the right-hand rear area for the
switching device and are accessi-
ble from the cable connection
department (see Fig.). Auxiliaries
are connected with flat-pin plug
6,3 x 0,8 mm.
d
Cable terminal
Cable terminal
Torque [Nm]
SE/SM Kabel
1 X 10 to 95
15
1 X 95 to 240
25
or
2 X 10 to 95
15
2 X 95 to 240
25
2 X 95 to 240
25
3ZX1012-0NJ61-2AN1