3. INSTALLATION AND CABLING

3.3.7 UTANK

The unit can be fixed to the wall or others fixtures of the installation by
means of the rear fixations.

3.4 NETWORK CABLING

NexU cabling has five wires (BLUE / WHITE / SCREEN / RED / BLACK).
Although is not compulsory to follow this sequence, it is highly
recommended to do so in order to follow this manual.
Following international conventions, blue / white and screen are used for
transferring information and red / black are used for supplying power (in
our case 24 VDC)
Not in all cases, all the elements have to be powered up by the network.
In some of the elements, power comes from external source.
As a brief summary:
• UDat / UDat Power+: 110 VAC / 240 VAC from customer power
electric network.
• UPower / UPower+: 110 VAC / 240 VAC from customer power
electric network.
• UValve: 24 VDC from NexU network.
• UCount: 24 VDC from NexU network.
• UView: 24 VDC from NexU network.
• UMeter/ UMeter+: 24 VDC from NexU network.
• UVision / UVision+: 24 VDC from NexU network.
• UPulser / UPulser+: 24 VDC from NexU network.
• UTank: 110 VAC / 240 VAC from customer power electric network.
• UNet: 110 VAC / 240 VAC from customer power electric network.
Note: As the CAN bus is a bus for industrial applications, it is protected
against interference and other disturbances that may exist in a workshop.
However, in order to function properly, the following rules must
be observed.
SAMOA Industrial, S.A. · Pol. Ind. Porceyo, I-14 · Camino del Fontán, 831 · 33392 - Gijón - Spain · Tel.: +34 985 381 488 · www.samoaindustrial.com
Units that are powered up by the customer power electric network,
transfer power to the units that are powered by the NexU network.
Therefore DO NOT POWER UP TWO UNITS AT THE SAME TIME FROM
DIFFERENT 110 VAC / 240 VAC SOURCES.
As a guideline, the maximum length of a wiring coming from a 110 VAC
/ 240 VAC source has to be:
Max Lenght =
2 < No. of Units < 8
• Always connect the armatures/shields at both ends of the line.
• Mains cables should not be laid close to or in parallel with
power supplies or power cables; if it is not possible to avoid crossing
these cables, it should be done at a 90° angle.
• If the power cable and mains cable must run in the same way, they
should be separated with the power cable on one side and
the mains cable on the other.
• Never connect power to equipment without first verifying
that the grounding wiring is done correctly.
EN
23
R. 06/21 838 861