Herunterladen Inhalt Inhalt Diese Seite drucken

Exchanging Frontplates - Camille Bauer SINEAX SV 824 Betriebsanleitung

Trennschaltverstarker
Vorschau ausblenden Andere Handbücher für SINEAX SV 824:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Maximum switching frequency
≤ 10 Hz
Input-relay output:
Signal input monitoring
Behaviour:
Circuit break and shorting are
signalled by the red LED and the
output of the corresponding
channel is disabled.
Pick-up level
according to
DIN EN 50 227:
Short-circuit I > approx. 6.3 mA
Open-circuit I < approx. 0.15 mA
Effectiveness of
input monitoring:
Enbalbed or disabled by switch
"
If the amplifier is a contact instead
of an active sensor and the input
circuit has to be monitored, two
resistors must be fitted close to the
contact as shown in Fig. 3.
Control circuit
Fig. 3. Input contact circuit.
Power supply H
AC/DC module (DC and 45...400 Hz)
Table 2: Nominal voltages and tolerances
Nominal voltage U
N
24... 60 V
DC / AC
85...230 V
AC
85...110 V
DC
≤ 1.4 W resp. ≤ 2.7 VA
Power input:
Electrical
isolation:
Signal inputs to output contacts
and power supply
Regulations
Electromagnetic
compatibility:
The standards DIN EN 50 081-2
and DIN EN 50 082-2 are observed
Intrinsically safe:
Acc. to DIN EN 50 020: 1994
Electrical standards:
Acc. to IEC 1010 resp. EN 61 010
Protection:
(acc. to IEC 529
resp. EN 60 529):
Housing IP 40
Terminals IP 20
20
All manuals and user guides at all-guides.com
".
≤ 200 Ω
1 to 2 kΩ
R
Ltg
Mecha-
10 to
nical
SINEAX SV 824
15 kΩ
contact
Tolerance
DC – 15...+ 33%
AC ± 15%
± 10%
– 15...+ 10%
Installation data
Terminals:
DIN/VDE 0609
Screw terminals with wire guards,
for light PVC wiring and
max. 2 × 0.75 mm
Vibration:
2 g acc. to EN 60 068-2-6
3 × 50 g
Shock:
3 shocks each in 6 directions
acc. to EN 60 068-2-27
Ambient conditions
Commissioning
–10 to + 55 °C
temperature:
Operating temperature: –20 to + 55 °C
– 40 to + 70 °C
Storage temperature:
Relative humidity
≤ 75%
of annual mean:

6. Exchanging frontplates

1
2
ON
ON
Fig. 4. Left: Removing the transparent cover
Right: Inserting the transparent cover.
Apply gentle pressure to the transparent cover as shown in
Fig. 4 until pops out on the opposite side. The label in the
cover can be replaced and used for notes.
After replacing the label in the transparent cover, the trans-
parent cover can be snapped into the front of the device
again. This is done by inserting if behind the edge at the
bottom and pressing it gently down and to the rear with the
finger until it snaps into place (right side of Fig. 4).
or 1 × 2.5 mm
2
2
1
2
ON
ON

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis