Herunterladen Inhalt Inhalt Diese Seite drucken

COMEM eSDB10 Bedienungsanleitung Seite 5

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 24
Self-monitoring function
The self-dehydrating air breather has a self-monitoring
function.
STANDARD CONFIGURATION
Malfunction
POWER FAILURE
SYSTEM FAILURE
Table 1
Outputs
STANDARD RELAY
USB
OPTIONS
ANALOG OUTPUT
DIGITAL OUTPUT RS-485
Table 2
Status indicators
Five LEDs which indicate the status of the device are
installed inside the terminal box and observable through
the glass.
Green LED (Fig.2/A):
Yellow LED (Fig.2/B):
Yellow LED (Fig.2/C):
Blue LED (Fig.2/D):
OFF: solenoid valve is:
- Red LED (Fig.2/E):
The display (Fig.2/F) shows information that is normally
displayed as:
• State (Fig.3/B):
- IDLE: normal functioning
- WARM UP CYL: heating tank 1 or 2
- DRYING CYL: maintenance at high temperatures in the
tank (1 or 2) during the regeneration phase
- COOL DOWN CYL: after the dehydrating phase
• Salt Saturation (Fig.3/A): Salt condition:
- 0%: completely dry
- 100%: saturation condition
• Alarm warning: an alarm warning is displayed on the
screen when a failure occurs. The warnings are:
- WARNING: FAN 1 FAIL and FAN 2 FAIL
(only for eSDB30 and eSDB40)
- HEATER 1 FAIL
- HEATER 2 FAIL
- TANK 1 NOT DRYED
- SALTS REPLACEMENT
What is detected
- Failure of the power supply
- Failure of the electronic circuit
- Failure of the heating element
- Failure of the weighing cell
STANDARD CONFIGURATION
1 x change over contact: POWER FAILURE
(terminals 22-24-21)
1 x change over contact: SYSTEM FAILURE
(terminals 12-14-11)
Interface to download relevant device data
4-20 mA (terminals 41-44)
(Minimum / Maximum resistance: 100 / 470 Ohm)
Digital Signal (terminals 3-4)
Power voltage ON
Regenerating tank ON
Regeneration tank 2
ON: eSDB15, eSDB30, eSDB40
solenoid valve is activated ;
pulsating (for eSDB40 only) tank
2 ON
disactivated
Alarm
When the device has got a failure, this is detected by
contacts that can be set in accordance to customer
demand on the following configuration:
SPECIAL CONFIGURATION
Malfunction
POWER FAILURE
SPECIAL CONFIGURATION
1 x NC contact: POWER FAILURE
(terminals 22-21)
1 x change over contact: HEATER ON
(terminals 12-14-11)
interface to download relevant device data
4-20 mA (terminals 41-44)
(Minimum / Maximum resistance: 100 / 470 Ohm)
Digital Signal (terminals 3-4)
A B
G
M
I
Figure 2
B
A
Figure 3
What is detected
- Failure of the power supply
- Failure of the electronic circuit
- Failure of the heating element
- Failure of the weighing cell
C D E
H
L
F
N
5

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für COMEM eSDB10

Diese Anleitung auch für:

Esdb15Esdb30Esdb40

Inhaltsverzeichnis