Series 8040
Non-Metallic Control
and Signaling Stations
Please read this entire document
before beginning any work.
1. Safety Instructions
Installation and maintenance of these control station
should only be performed by qualified personnel in
accordance with the National Electrical Code (NFPA
70) or the Canadian Electrical Code (CEC) and any
local regulations which relate to hazardous (classi-
fied) locations.
CAUTION:
• Disconnect power supply before installing or serv-
icing these control stations.
• Operate only undamaged devices with observa-
tions of the operating parameters in Section 2.
• For a Class I Zone 1 conduit installation, conduit
seals are required, refer to NEC 505.16 (B) (1).
For any other cable or conduit installation NO
seals are required.
• Use only approved wiring methods for the location,
with the appropriate conduit/cable fittings.
2. Certification
NEC
Class I, Zone 1 & 2, AEx ed IIC T6; IP66
Class I, Div. 2, Groups ABCD
Class II, Div. 2, Groups FG; Class III
Enclosure Type 3, 4, 4X
Listed - File No. E182378
R
CEC
Class I, Zone 1 & 2, Ex ed IIC T6; IP66
Class I, Div. 2, Groups ABCD
Class II, Div. 1 & 2, Groups EFG; Class III
®
Enclosure Type 3, 4, 4X
Certified - File No. LR99480-26
II 2 G EEx ed IIC T6; IP66
PTB 01 ATEX 1105
80 406 10 30 0
8040606300
S-BA-8040-en-02-15/06/2007
Installation, Operation & Maintenance Sheet
INSTALLATION OPERATION
& MAINTENANCE SHEET
3. Component Data
3.1
Pilot Light, type 8010:
12V - 254V AC/DC, 0-60Hz
Terminal capacity 12-22 AWG. or 2.5 mm
tightened to 18 in-lbs. or 2 N-m
3.2
Contact Block, type 8082:
600V, 10A max.
Terminal capacity 12-22 AWG. or 2.5 mm
ened to 18 in-lbs. or 2 N-m
3.3
Control Switch, type 8008/2-0...and 8008/2-1..:
600V, 10A max.
Terminal capacity 12-22 AWG. or 2.5 mm
tightened to 18 in-lbs. or 2 N-m.
3.4
Ammeter, type 8405:
600V, Ampere rating see data on device
Terminal capacity 12-22 AWG. or 2.5 mm
tightened to 18 in-lbs. or 2 N-m.
4. Directions for Installation
4.1
Mounting the Enclosure
Using a common screwdriver, remove the four
cover screws. Install the enclosure securely
using #10 to 1/4" (or M5 to M6) mounting
screws, through holes are provided in the box.
Mounting dimensions are as shown on page 3.
4.2
Electrical Installation
There are two types of installation methods:
Conduit installation and cable installation. When
conduit is used the control station(s) were
ordered and delivered with a 3/4" conduit hubs.
When MC-HL cable is used the control station
comes with internal ground plates, with NPT
threads into which the appropriate cable connec-
tors with sealing rings have to be fitted.